Highlights of NFPA 101

The Life Safety Code - 1997 Regarding Doors, Frames, & Hardware

Locks, Latches, and Alarm Devices (5-2.1.5)

  1. locks shall not require the use of a key, tool, or special knowledge or effort for operation from the inside of the building...
  2. where permitted by chapters 8-31, key operation shall be permitted, provided that the key can’t be removed when the door is locked from the egress side

Stairwell Reentry (2-5.1.5.2)

  1. every stair enclosure door shall permit reentry to the interior of the building, or an automatic release shall be provided to unlock all stair doors simultaneously upon initiation of the building fire alarm system
  2. selected doors shall be permitted to have locking hardware, provided that
  3. stairs serving less than 4 stories do not need to comply
  4. existing installations as permitted in chapters 8-31 do not need to comply
  5. stairs serving a building permitted to have a single exit in accordance with chapters 8-32 do not need to comply
  6. compliance is not necessary where specifically allowed by chapters 12 or 14

Releasing Devices (5-2.1.5.3)

  1. latch or fastening device shall be provided with a releasing device having an obvious method of operation under all lighting conditions.
  2. releasing mechanism shall be located not more than 48” a.f.f.
  3. doors shall be openable with not more than one releasing operation
  4. each leaf of a pair in a means of egress shall have it’s own releasing device, and each device has to operate independently (can’t require 1 device to be released before the other), except
  5. no additional locking device (padlock, hasp, chain, deadbolt, etc.) shall be installed on a door which requires panic hardware

Delayed Egress Locks (5-2.1.6.1)

  1. approved, listed, delayed egress locks shall be permitted in buildings protected by an approved fire detection system or sprinkler system, where permitted by chapers 8-31, provided that

Access-Controlled Egress Doors (5-2.1.6.2)

  1. where permitted in chapters 8-32, doors in the means of egress shall be permitted to have an approved entrance and egress access control system, provided that

Panic Hardware (5-2.1.7)

  1. actuating portion of device extends at least 1/2 the width of the door leaf
  2. device must be mounted between 30” and 44” a.f.f.
  3. requirements for which doors must have panic devices are listed within the individual occupancy chapters - means of egress doors in assembly and education occupancies with an occupant load of 100 or more persons shall be permitted to have a latch or lock only if it is panic hardware

Closers (5-2.1.5.3)

  1. doors designed to normally be kept closed in a means of egress shall be a self-closing door and shall not be secured in the open position, except where allowed by NFPA 101 or the ahj, doors can be automatic closing, permitted that

Note: A standard door closer with no hold-open mechanism is self-closing. A door closer with an electric or battery-operated hold-open mechanism actuated by the fire protection system is automatic-closing.